CO₂ has been discharged. The ER has been sealed for 20 minutes. The chief engineer says "The fire is probably out — let me go in to check and start getting the emergency generator sorted." The vessel is now drifting without propulsion. Wind is pushing the vessel toward shallow water (18nm, approximately 4 hours at current drift rate). Can the chief engineer re-enter?

A. No. Minimum hold time after CO₂ discharge is typically at least 30 minutes for smouldering fires — and an ER bilge fire involving oil can re-ignite if the fuel source has not been physically isolated. Re-entry requires BA, a charged hose in position, a boundary cooling check, and a charged fire party standing by outside. 20 minutes is insufficient
B. Yes — 20 minutes is sufficient for CO₂ to have worked. The pressure of drifting toward shallow water justifies early entry
C. Yes if he wears a smoke hood and keeps the door propped open for ventilation
D. Allow entry to the ER lobby only, not the bilge area
Sign in or create a free account to see the answer and explanation.
MV SOLWAY STAR, 1435. The engine room fixed fire detection alarm activates on the bridge panel — zone indicated is bilge area, below the main engine. The ER is manned — the chief engineer and two ratings are on watch below. What is the OOW's FIRST action?
A. Sound the general alarm immediately. Inform the Master. Do NOT ring the engine room to ask them to investigate — they are in the fire zone. The general alarm brings the emergency team to their stations and ensures the CO₂ room and fire parties are ready before any further assessment
B. Ring the engine room first to check if it is a real fire or a sensor fault — this avoids a false alarm muster
C. Go to the CO₂ room and stand by to discharge — you may need to act quickly
D. Alert the chief officer and wait for his assessment before sounding general alarm
Sign in or create a free account to see the answer and explanation.
Thirty seconds after the general alarm, the chief engineer radios the bridge: "I can see smoke near the bilge pump. I'm going to check if it's a small oil fire — I'll call you back in two minutes." The fire party is mustering on deck. What is the Master's response?
A. Order the chief engineer and ALL engine room personnel to evacuate immediately and close the ER fire dampers and watertight doors. Do not allow investigation without full BA team and hose in place. Smoke in an ER bilge area of a naphtha carrier is a serious fire risk — vapour ignition can occur in seconds
B. Allow the chief engineer to investigate — he knows the space and if it is small it is better to tackle it immediately
C. Tell the chief engineer to use the local CO₂ extinguisher first and report back
D. Wait the two minutes before taking any further action
Sign in or create a free account to see the answer and explanation.